Knowledge Search
Download document () of 20
Back-up power (UPS)

Eaton 93PM UPS

The Eaton 93PM UPS is the perfect three-phase white or gray space solution for modern data centers. The 93PM is compatible with lithium-ion UPS batteries, which are 40 percent smaller than VRLA batteries and have twice the lifespan, saving money on battery replacement costs and extra square footage for battery cabinets. The option of front-to-back or front-to-top ventilation maximizes deployment flexibility and lowers your cooling costs. In addition, you can add a number of optional, full integrated accessories for a complete system, including a maintenance bypass, a distribution cabinet (with input and output transformer options), a power distribution cabinet, parallel tie cabinets and battery cabinets as well as a wall-mounted or floor mounted bypass. Whether for a large data center, medical facility or educational institution, the efficiency provided by the 93PM can play a vital role in any low maintenance, ten-year power solution.

Power rating
10-400 kW
Voltage
480V, 208V, or 220V
Configuration
Tower

Easy deployment

● Maximizes deployment flexibility with thermal management options, flexible configurability and full-service access from the front
● Simplifies installation by fitting perfectly in line or alongside any standard-depth rack

93PM UPS videos

    Ease of management

    ● Provides easier access to detailed status information
    ● Optimizes server virtualization through power management and connectivity software
    ● Increases uptime with 24x7 remote monitoring and reporting capabilities

    Lowest Total Cost of Ownership (TCO)

    ● Reduces power and cooling
    ● Conserves valuable data center floor space
    ● Reduces cost and unexpected future growth risks

    Eaton lithium-ion batteries

    The weight and dimensional benefits of lithium-ion battery cabinets create the optimal solution for your white or gray space.

    Warranty and service plans

    Eaton's UPS warranty and service options provide the system uptime, convenience and value that is right for you and your business.

    Available as an emergency lighting UPS

    Specifications

    Product snapshot

    POWER RATING

    10-400kW

    VOLTAGE

    480V, 208V, or 220V

    FREQUENCY

    50/60 Hz

    TOPOLOGY

    Double conversion with optional Energy Saver System (ESS)

    EFFICIENCY

    Up to 97% in double conversion
    Up to 99% in Energy Saver System

    SCALABILITY

    480V model: up to 8 internal power modules
    208/220V model: up to 10 internal power modules
    External parallel up to 8 UPSs

    CONFIGURATION

    Tower

    BATTERIES

    480V model: Internal batteries up to 50 kW
    208/220V model: Internal batteries up to 60 kW
    External batteries up to 400 kW

    Dimensions and weights (mm/inches)

    HEIGHT
    WIDTH
    DEPTH
    93PM UPS - 20-150 KW (480V) AND 10-120 KW (208/220V)
    HEIGHT

    1880/74

    WIDTH

    559/22

    DEPTH

    1067/42

    93PM UPS - 160-200 KW (480V)
    HEIGHT

    1880/74

    WIDTH

    813/32

    DEPTH

    1067/42

    93PM UPS - 125-160 KW (208-220V)
    HEIGHT

    1880/74

    WIDTH

    870/34.25

    DEPTH

    1067/42

    93PM UPS - 165-200 KW (208-220V)
    HEIGHT

    1880/74

    WIDTH

    1100/43.3

    DEPTH

    1067/42

    93PM UPS - 250-400 KW (480V)
    HEIGHT

    1880/74

    WIDTH

    1623/64

    DEPTH

    1067/42

    Due to continuing improvements, specifications are subject to change without notice.

    UPS rating (1.0 power factor)

    93PM 480V
    93PM 208/220V
    KW
    93PM 480V

    20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 120, 130, 140, 150, 160, 170, 180, 190, 200, 250, 300, 350, 400

    Optional internal redundancy

    93PM 208/220V

    10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 65, 70, 75, 80, 85, 90, 95, 100, 105, 110, 115, 120, 125, 130, 135, 140, 145, 150, 160, 165, 170, 175, 180, 185, 190, 195, 200

    Optional internal redundancy

    General characteristics

    93PM 480V
    93PM 208/220V
    AUDIBLE NOISE
    93PM 480V

    65 dBA at 200 kW, 76 dBA at 400 kW

    93PM 208/220V

    65 dBA at 200 kW, 76 dBA at 400 kW

    ALTITUDE (MAX)
    93PM 480V

    1,500 meters / 4,922 feet

    93PM 208/220V

    1,500 meters / 4,922 feet

    SCALABILITY
    93PM 480V

    Up to 8 internal power modules

    External parallel with up to 8 UPSs

    93PM 208/220V

    Up to 10 internal power modules

    External parallel with up to 4 UPSs (400 kW max)

    EFFICIENCY
    93PM 480V

    93PM efficiency with ESS- up to 99%

    93PM double-conversion efficiency- up to 97% Input Characteristics

    93PM 208/220V

    93PM efficiency with ESS- up to 99%

    93PM double-conversion efficiency- up to 97% Input Characteristics

    Input characteristics

    93PM 480V
    93PM 208/220V
    VOLTAGE
    93PM 480V

    480 3-phase, 3-wire or 4-wire (208 or 220 3-phase 3-wire with IAC-D)

    93PM 208/220V

    208 or 220 3-phase 4-wire

    VOLTAGE RANGE
    93PM 480V

    +10% / -15%

    93PM 208/220V

    +15% / -15% at 208V

    +10% / -15% at 220V

    FREQUENCY RANGE
    93PM 480V

    50/60 Hz

    93PM 208/220V

    50/60 Hz

    POWER FACTOR
    93PM 480V

    > .99

    93PM 208/220V

    > .99

    INPUT CURRENT DISTORTION
    93PM 480V

    ≤3.5% @ 100% load capacity

    93PM 208/220V

    ≤3.5% @ 100% load capacity

    SOFT START CAPABILITY
    93PM 480V

    Yes

    93PM 208/220V

    Yes

    BACKFEED PROTECTION
    93PM 480V

    Internal contactor

    93PM 208/220V

    Internal detection with external shunt trip protection

    Output characteristics

    93PM 480V
    93PM 208/220V
    VOLTAGE
    93PM 480V

    480 3-phase, 3-wire or 4-wire (208V or 220V 3-phase 3-wire or 4-wire with IAC-D)

    93PM 208/220V

    208V or 220V 3-phase 3-wire or 4-wire

    REGULATION
    93PM 480V

    ±1% steady state

    93PM 208/220V

    ±1% steady state

    INVERTER
    93PM 480V

    PWM with IGBT Switching

    93PM 208/220V

    PWM with IGBT Switching

    VOLTAGE THD
    93PM 480V

    < 1% (100% linear load)

    < 5% (non-linear load)

    93PM 208/220V

    < 1.6% (100% linear load)

    < 5% (non-linear load)

    LOAD POWER FACTOR RANGE
    93PM 480V

    Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating

    93PM 208/220V

    Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating

    HEAT DISSIPATION (BTU/HR X 1000/HR)
    93PM 480V

    20 kW, 2.55
    30 kW, 3.58
    40 kW, 4.56
    50 kW, 5.70
    60 kW, 7.16
    70 kW, 8.36
    80 kW, 9.12
    90 kW, 10.26
    100 kW, 11.40
    110 kW, 12.54
    120 kW, 13.68
    130 kW, 14.82
    140 kW, 15.96
    150 kW, 17.10
    160 kW, 18.24
    170 kW, 19.38
    180 kW, 20.52
    190 kW, 21.66
    200 kW, 22.80
    250 kW, 28.50
    300 kW, 34.20
    350 kW, 39.90
    400 kW, 45.60

    93PM 208/220V

    10 kW, 0.9
    15 kW, 1.35
    20 kW, 1.8
    25 kW, 2.24
    30 kW, 2.69
    35 kW, 3.14
    40 kW, 3.59
    45 kW, 4.04
    50 kW, 4.49
    55 kW, 4.94
    60 kW, 5.39
    65 kW, 5.83
    70 kW, 6.28
    75 kW, 6.73
    80 kW, 7.18
    85 kW, 7.63
    90 kW, 8.08
    95 kW, 8.53
    100 kW, 8.98
    105 kW, 9.42
    110 kW, 9.87
    115 kW, 10.32
    120 kW, 10.77
    125 kW, 11.22
    130 kW, 11.67
    135 kW, 12.12
    140 kW, 12.57
    145 kW, 13.01
    150 kW, 13.46
    155 kW, 13.91
    160 kW, 14.36
    165 kW, 14.81
    170 kW, 15.26
    175 kW, 15.71
    180 kW, 16.16
    185 kW, 16.6
    190 kW, 17.05
    195 kW, 17.5
    200 kW, 17.95

    Battery

    93PM 480V
    93PM 208/220V
    BATTERY TYPE
    93PM 480V

    VRLA, Wet Cell, Lithium-ion

    93PM 208/220V

    VRLA, Wet Cell, Lithium-ion

    BATTERY VOLTAGE
    93PM 480V

    432V (3-wire systems only), 480V

    93PM 208/220V

    480V

    CHARGING METHOD
    93PM 480V

    ABM or float technology

    93PM 208/220V

    ABM or float technology

    Serviceability

    93PM 480V
    93PM 208/220V
    BACK/SIDE AGAINST WALL INSTALLATION
    93PM 480V

    Standard, front access only

    93PM 208/220V

    Standard, front access only

    Certification

    93PM 480V
    93PM 208/220V
    SAFETY
    93PM 480V

    UL 1778, cULus, UL 924 Emergency, UL 924 Auxiliary

    93PM 208/220V

    UL1778, cULus

    EMC
    93PM 480V

    FCC Part 15 Subpart B Class A

    93PM 208/220V

    FCC Part 15 Subpart B Class A

    SURGE
    93PM 480V

    IEC 61000-4-5

    93PM 208/220V

    IEC 61000-4-5

    UL 924
    93PM 480V

    The 93PM meets the strict standards for UL 924 compliance for emergency lighting applications when ordered with an emergency lighting SKU. For more information, visit Eaton.com/UL924UPS.

    93PM 208/220V

    Pending

    Optional line and match accessories

    93PM 480V AND 93PM 208/220V
    • External slim maintenance bypass 
    • Integrated distribution cabinet (with input and output transformer options) 
    • Integrated power distribution cabinet 
    • Integrated parallel tie cabinet 
    • Integrated battery cabinet (small and large) 
    • Wall-mounted or floor mounted bypass 
    • Lithium battery cabinet

    PredictPulse remote monitoring service

    93PM 480V AND 93PM 208/220V
    24x7 remote monitoring of UPS and battery alarms, online dashboard for real-time updates, mobile app for alarms and monthly report. PredictPulse requires the PXGX-UPS Card and Environmental Monitoring Probe.

    Communication options

    THE FOLLOWING CONNECTIVITY OPTIONS CAN BE INSTALLED AT ANY TIME:
    INTELLIGENT POWER SOFTWARE

    Eaton’s Intelligent Power Manager software enables you to:

    • Remotely monitor and manage multiple devices across your network from a single interface; this can be integrated into an already existing platform, such as VMware, Microsoft or Citrix
    • Measure power consumption and kWh to calculate power usage effectiveness
    • Trigger load shedding of lesser priority server workloads to extend battery run time in a virtualized environment.
    • Trigger workload transfer to disaster recovery site with no loss of data, using VMware’s Site Recovery Manager.

    Eaton’s Intelligent Power Protector software enables you to:

    • Reboot hung-up machines through watchdog functionality
    • Avoid data loss by automating graceful shutdown of machines during extended power outage
    • Maximize uptime with redundancy capabilities for dual-cord servers
    Download Links