The Eaton 93PM UPS is the perfect three-phase white or gray space solution for modern data centers. The 93PM is compatible with lithium-ion UPS batteries, which are 40 percent smaller than VRLA batteries and have twice the lifespan, saving money on battery replacement costs and extra square footage for battery cabinets. The option of front-to-back or front-to-top ventilation maximizes deployment flexibility and lowers your cooling costs. In addition, you can add a number of optional, full integrated accessories for a complete system, including a maintenance bypass, a distribution cabinet (with input and output transformer options), a power distribution cabinet, parallel tie cabinets and battery cabinets as well as a wall-mounted or floor mounted bypass. Whether for a large data center, medical facility or educational institution, the efficiency provided by the 93PM can play a vital role in any low maintenance, ten-year power solution.
10-400kW
480V, 208V, or 220V
50/60 Hz
Double conversion with optional Energy Saver System (ESS)
Up to 97% in double conversion
Up to 99% in Energy Saver System
480V model: up to 8 internal power modules
208/220V model: up to 10 internal power modules
External parallel up to 8 UPSs
Tower
480V model: Internal batteries up to 50 kW
208/220V model: Internal batteries up to 60 kW
External batteries up to 400 kW
1880/74
559/22
1067/42
1880/74
813/32
1067/42
1880/74
870/34.25
1067/42
1880/74
1100/43.3
1067/42
1880/74
1623/64
1067/42
20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 120, 130, 140, 150, 160, 170, 180, 190, 200, 250, 300, 350, 400
Optional internal redundancy
10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 65, 70, 75, 80, 85, 90, 95, 100, 105, 110, 115, 120, 125, 130, 135, 140, 145, 150, 160, 165, 170, 175, 180, 185, 190, 195, 200
Optional internal redundancy
65 dBA at 200 kW, 76 dBA at 400 kW
65 dBA at 200 kW, 76 dBA at 400 kW
1,500 meters / 4,922 feet
1,500 meters / 4,922 feet
Up to 8 internal power modules
External parallel with up to 8 UPSs
Up to 10 internal power modules
External parallel with up to 4 UPSs (400 kW max)
93PM efficiency with ESS- up to 99%
93PM double-conversion efficiency- up to 97% Input Characteristics
93PM efficiency with ESS- up to 99%
93PM double-conversion efficiency- up to 97% Input Characteristics
480 3-phase, 3-wire or 4-wire (208 or 220 3-phase 3-wire with IAC-D)
208 or 220 3-phase 4-wire
+10% / -15%
+15% / -15% at 208V
+10% / -15% at 220V
50/60 Hz
50/60 Hz
> .99
> .99
≤3.5% @ 100% load capacity
≤3.5% @ 100% load capacity
Yes
Yes
Internal contactor
Internal detection with external shunt trip protection
480 3-phase, 3-wire or 4-wire (208V or 220V 3-phase 3-wire or 4-wire with IAC-D)
208V or 220V 3-phase 3-wire or 4-wire
±1% steady state
±1% steady state
PWM with IGBT Switching
PWM with IGBT Switching
< 1% (100% linear load)
< 5% (non-linear load)
< 1.6% (100% linear load)
< 5% (non-linear load)
Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating
Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating
20 kW, 2.55
30 kW, 3.58
40 kW, 4.56
50 kW, 5.70
60 kW, 7.16
70 kW, 8.36
80 kW, 9.12
90 kW, 10.26
100 kW, 11.40
110 kW, 12.54
120 kW, 13.68
130 kW, 14.82
140 kW, 15.96
150 kW, 17.10
160 kW, 18.24
170 kW, 19.38
180 kW, 20.52
190 kW, 21.66
200 kW, 22.80
250 kW, 28.50
300 kW, 34.20
350 kW, 39.90
400 kW, 45.60
10 kW, 0.9
15 kW, 1.35
20 kW, 1.8
25 kW, 2.24
30 kW, 2.69
35 kW, 3.14
40 kW, 3.59
45 kW, 4.04
50 kW, 4.49
55 kW, 4.94
60 kW, 5.39
65 kW, 5.83
70 kW, 6.28
75 kW, 6.73
80 kW, 7.18
85 kW, 7.63
90 kW, 8.08
95 kW, 8.53
100 kW, 8.98
105 kW, 9.42
110 kW, 9.87
115 kW, 10.32
120 kW, 10.77
125 kW, 11.22
130 kW, 11.67
135 kW, 12.12
140 kW, 12.57
145 kW, 13.01
150 kW, 13.46
155 kW, 13.91
160 kW, 14.36
165 kW, 14.81
170 kW, 15.26
175 kW, 15.71
180 kW, 16.16
185 kW, 16.6
190 kW, 17.05
195 kW, 17.5
200 kW, 17.95
432V (3-wire systems only), 480V
480V
ABM or float technology
ABM or float technology
Standard, front access only
Standard, front access only
UL 1778, cULus, UL 924 Emergency, UL 924 Auxiliary
UL1778, cULus
FCC Part 15 Subpart B Class A
FCC Part 15 Subpart B Class A
IEC 61000-4-5
IEC 61000-4-5
The 93PM meets the strict standards for UL 924 compliance for emergency lighting applications when ordered with an emergency lighting SKU. For more information, visit Eaton.com/UL924UPS.
Pending
Eaton’s Intelligent Power Manager software enables you to:
Eaton’s Intelligent Power Protector software enables you to: