The Power Xpert 9395 UPS provides industry-leading efficiency and scalable battery runtimes in a small footprint. A modular UPS, the Power Xpert 9395 UPS is suited for large data centres, healthcare applications, multi-tenant data centres, light industry and other critical systems can lower their total cost of ownership. Monitor and manage your 9395 UPS with the colour LCD touchscreen display.
Starting in January 2022, PredictPulse Wireless will be installed at no extra charge for all Power Xpert 9395 UPS models! The best news is that Eaton service technicians will install and activate this service during start-up using a mobile broadband modem/router, streamlining the set-up process for customers at no charge for one year for products sold after 1 January 2022!
UPS rating (0.91 power factor) | |
kVA | 225, 275, 450, 500, 550, 650, 750, 825, 1000, 1100 |
kW | 202, 250, 405, 450, 500, 585, 675, 750, 900, 1000 |
General characteristics | |
Efficiency | >94% (99% with ESS) |
Parallel capability | 4 distributed, 32 with SBM |
Max modules per size | Up to 3 modules, 550 kVA, up to 4 modules, 825/1100 kVA |
Audible noise | <76dBA @ 1 metre |
Altitude (max) | 2000m at 40ºC (104ºF) |
N+1 redundancy capable | Yes |
Field upgradeable | Yes |
System bypass module | Included |
Control panel (LCD) | Colour touchscreen with LED panel |
Battery start-up | Standard |
Frequency conversion | Standard |
Multi-language | Standard |
Building alarm inputs | 5 (galvanic isolated) |
Input characteristics | |
Voltage | 480V standard; and 400V available |
Voltage range | +10%/-15% |
Frequency range | 45–65 Hz |
Power factor | 0.99 (minimum) |
Input current distortion | <3.5% (no input filter required) |
Soft-start capability | Yes |
Internal backfeed protection | Yes |
Output characteristics | |
Voltage | 480V standard; and 400V available |
Regulation | ±1% |
Inverter | PWM with IGBT switching |
Voltage | THD <2% (100% linear load); <5% (non-linear load) |
Load power factor range | Up to a .9 power factor leading without derating |
Battery | |
Battery types | VRLA, AGM, wet cell |
Battery voltage | 480V |
Temperature compensation | Optional |
Charging method | ABM technology or float, selectable |
Dimensions and weights | |
225 kVA, 275 kVA |
52.4”w x 32.7”d x 73.6”h (1,786 lb) |
225 kVA redundant, 275 kVA redundant | 73.7”w x 32.7”d x 73.6”h (2,875 lb) |
450, 500, 550 kVA | 73.7”w x 32.7”d x 73.6”h (2,977 lb) |
450, 550 kVA redundant | 103”w x 32.7”d x 73.6”h (4,153 lb) |
Field upgrade module, 225 or 275 kVA | 30”w x 32.7”d x 73.6”h (1,176 lb) |
650, 750, 825 kVA | 140.9"w x 32.7"d x 73.7"h (5,065 lb) |
650, 750, 825 kVA +1 redundant | 170.2"w x 32.7"d x 73.7"h (6,365 lb) |
1000, 1100 kVA | 170.2"w x 32.7"d x 73.7"h (6,525 lb) |
Certification | |
Safety | UL1778, cUL |
EMC | IEC 62040-2, EN50091 class A (restricted access) |
Options |
|
Communication cards | Four communication bays as standard. The following connectivity options can be installed at any time:
|
Remote inputs/outputs: Five building alarm inputs and one summary alarm contact (5A @ 120V) as standard Remote monitor panel: Eight backlit status indicator lamps plus an audible horn |
|
Software compatibility |
|
Support from Eaton
Contact me
Phone: (800) 843 9433
Or visit our tech support knowledge base