Tripp Lite series SmartOnline 5000VA 4500W 208V Online Double-Conversion UPS - L6-30P, 2 L6-20R, 2 L6-30R, Hardwired Output, Network Card, Extended Run, 3U Rack/Tower
Product Name |
Eaton Tripp Lite series SmartOnline UPS
|
Catalog Number |
SU5000RT
|
UPC |
786689811723
|
Product Length/Depth |
25.04 in
|
Product Height |
5.12 in
|
Product Width |
17.32 in
|
Product Weight |
114.02 lb
|
Compliances |
FCC Compliant
CE Marked RoHS FCC Class A ENERGY STAR certified REACH |
Certifications |
NOM
IEC/EN 62040-2 CSA 22.2 UL 1778 cTUVus |
Global Catalog |
SU5000RT
|
Battery replacement |
EBP-1803
|
Battery type |
Valve Regulated Lead Acid (VRLA)
|
Extended battery capability |
Add up to 4 extended battery modules (EBM). Part number BP180RT
|
Runtime at full load |
3 min. (4500W)
|
Runtime at half load |
11 min
|
High Voltage Transfer to Battery Power |
276V
|
Low Voltage Transfer to Battery Power |
176V
|
Output Voltage Regulation (Line Mode) |
+/- 1%
|
Output Voltage Regulation(Battery Mode) |
+/- 1%
|
Receptacle |
(2) L6-20R; (2) L6-30R; Hardwire
|
Topology |
Online/Double-conversion
|
Wattage |
4500 W
|
Output waveform |
True sine wave
|
Output power factor |
0.9
|
Voltage |
208 V
|
Output nominal voltage |
208V default (200/208/220/230/240V)
|
Output frequency |
50/60 Hz
|
Number of Outputs L6-20R |
2
|
Number of Outputs L6-30R |
2
|
Number of outputs hardwired |
1
|
Current Crest Ratio |
3:1
|
Input connection |
Hardwire; L6-30P
|
Input cord length |
10 ft
|
Input nominal voltage |
200 VAC/208 VAC/220 VAC/230 VAC/240 VAC
|
Input voltage range |
200-240V
|
Input power factor |
>0.99 typical
|
AC suppression joule rating |
390
|
Input Circuit Breakers |
Recommended 30A upstream
|
Ethernet interface |
Yes
|
Includes network card |
Yes
|
Software compatibility |
PowerAlert
|
Altitude |
<1000m for nominal power, 10% power degrading every 1000m (up to 3000m)
|
Noise level |
<45 dB at 1 meter
|
Relative humidity |
0-95% non-condensing
|
Storage Temperature |
With battery: 32° to 104°F (0° to 40°C); without battery: -13° to 131°F (-25° to 55°C)
|
Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
Form factor |
Rack/tower
|
Rack size |
3U
|
Rack mounting kit |
Yes
|
Efficiency at max. load |
93%
|
Switch configuration |
RPO / ROO
|
Phase (input) |
Single-phase
|
Surge protection |
Yes
|
Internal bypass |
Yes
|
Package contents |
|
Total Harmonic Distortion |
< 2% THDV on linear load; < 5% THDV on non-linear load
|
EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
Green Energy-Saving Features |
High efficiency economy mode operation
|
Standard factory warranty |
|
Extended service plans |
|